
Fire protection systems – classification
Depending on the extinguishing agent used, fire protection (fire suppression) systems can be divided into:
- Water-based systems (sprinkler and drencher systems) – they spray water directly over the seat of the fire. Their main advantage is high effectiveness in buildings where fire can spread quickly or where the building needs to be cooled.
- Water mist systems – they break water up into droplets smaller than 50 µm, which evaporate rapidly at high temperature. This cools the fire area and at the same time displaces oxygen around the seat of the fire. These systems use less water than sprinkler systems and limit water damage.
- Foam systems – they cut the fire off from oxygen by covering or filling the burning object with foam. Foam systems are built in a similar way to water systems: foam concentrate is added to the water and the mixture is aerated. At the end of the installation, foam branch pipes, eductors, foam chambers, water/foam monitors or foam pourers are used. Their advantages are that they separate the fire from the combustible material and do not flood the protected area.
- Gas systems – they displace oxygen from the protected space and/or interrupt the chemical combustion reaction. Gaseous extinguishing is the best choice for protecting electronic equipment, because extinguishing gases do not conduct electricity.
- Powder systems – they use the anticatalytic (inhibiting) effect of extinguishing powder to stop combustion. They are used where other systems cannot be applied or would not be cost-effective. Their advantages are effectiveness at sub-zero temperatures and harmlessness to the natural environment.
Extinguishing systems can also be classified by the type of area they protect. Large-volume buildings are most often protected by water, foam or water mist systems, while rooms of up to approx. 1000 m3 are usually protected by gas systems. In smaller buildings, drencher systems or water mist systems can be used. Fires starting in machinery and electrical equipment can be extinguished by gas systems or by dedicated local solutions, such as automatic detection tube systems installed directly in machines and electrical cabinets.
Passive fire protection
Another method of fire prevention is passive fire protection. It slows down or stops the spread of fire by means of suitable materials and products integrated into the building structure (e.g. fire-resisting walls and floors, fire doors, fire dampers) and by fire safety procedures. It is complemented by fire detection and alarm systems, which include a voice alarm system (VAS).
The fire detection and alarm system detects a fire at an early stage and transmits the information to the control panel, which alerts the responsible persons or organisations (e.g. the fire and rescue service). The voice alarm system broadcasts warning signals and voice messages, which are triggered automatically by a signal from the fire detection and alarm system.
Smoke extraction ventilation – types of smoke control systems
Smoke control systems are designed to remove fire gases (smoke) from rooms and replace them with fresh air, equalising the pressure differences created by the fire and allowing occupants to breathe. Smoke control systems can be divided into:
- gravity (natural) systems,
- mechanical systems,
- mixed systems,
- overpressure (pressurisation) systems.
Natural (gravity) smoke ventilation relies primarily on convection, i.e. the rise of hot smoke.
Mechanical smoke extraction uses various mechanical devices (fans, jet fans) to move fire gases. These devices may form part of a smoke extraction system or act as individual smoke extraction points.
Mixed (hybrid) smoke control systems combine the functions of smoke extraction and smoke prevention.
Pressurisation (overpressure) systems – their main purpose is to keep smoke out. The basic principle is to define the direction of airflow (pressure gradient): the highest pressure is maintained on the escape routes.
Smoke control systems can also be divided into ducted systems (smoke rises vertically and is extracted through a network of exhaust ducts) and ductless systems (air and smoke are moved horizontally – jet ventilation).
Where should fire protection systems be used?
Fire protection systems should, as far as possible, be used in all buildings where people are present and where the results of their work are stored. National fire regulations specify which buildings must be fitted with fire detection and alarm systems – the thresholds (number of seats, beds or occupants, floor area, number of storeys) differ from country to country. Typically, the obligation covers:
- retail and exhibition buildings,
- theatres with a large number of seats,
- cinemas with a large number of seats,
- restaurants and other catering premises for a large number of guests,
- sports and entertainment halls,
- hospitals and sanatoria,
- psychiatric hospitals,
- care homes and rehabilitation centres for people with disabilities,
- workplaces employing a large number of people with disabilities,
- high-rise public buildings,
- hotels, halls of residence and other buildings with many sleeping places,
- state archives,
- museums and listed historic buildings,
- server rooms and data centres,
- telephone exchanges,
- underground car parks – especially those with a large fire compartment or more than one underground level,
- metro and underground railway stations,
- railway stations used by large numbers of people at the same time,
- banks with large customer halls,
- libraries holding old prints, and archives.
Smoke control systems – components
A traditional ducted smoke ventilation system consists of the following components:
Particular attention should be paid to escape routes and to areas such as staircases and car parks. Smoke and fire gases make evacuation impossible because of the risk of poisoning by combustion products. Fire ventilation controls the flow of air and smoke so that smoke and gases are removed to the outside as quickly as possible and people can escape.
Fire ventilation – types
Depending on the objective and the type of equipment used, fire ventilation systems can be divided as follows [1]:
- smoke and heat exhaust ventilation (SHEVS – Smoke and Heat Exhaust Ventilation System) – removes smoke from the layer accumulated below the ceiling and maintains a smoke-free layer through which people can escape,
- smoke and heat control system – keeps the smoke within a defined area between the seat of the fire and the point of extraction, giving fire and rescue teams easy access to the fire,
- smoke clearance (dilution) – removes smoke and mixes it with incoming make-up air to reduce its temperature and toxicity.
Types of fire ventilation systems – diagrams
Human life and health depend on the correct operation of the fire ventilation serving escape routes.
Fire ventilation – diagrams showing how the different systems work
For a ducted system (Fig. 3) to work properly, the car park must be divided into smoke zones by smoke curtains (1), which prevent smoke from spreading to the rest of the car park. Smoke produced by the fire is extracted through grilles on the ventilation ducts (2). A clear division forms between the hot smoke layer below the ceiling and the smoke-free layer (3). Make-up air is supplied in a way that does not cause the smoke to descend (4).
Exhaust grilles are located at two heights above floor level (Figs. 4 and 5):
- more than 1.8 m above the floor – removing lighter pollutants,
- less than 0.8 m above the floor – removing pollutants that are heavier than air.
In normal operation, approx. 60% of the air is extracted from below the ceiling and the remaining 40% at floor level. In the event of fire, the lower extraction is shut off and 100% of the smoke extraction airflow should be drawn through the upper grilles.
Smoke control in buildings – regulatory requirements
A smoke extraction system should remove smoke at a rate which ensures that, for the time needed to evacuate people, protected corridors and escape routes remain free of smoke and of temperatures that would prevent safe evacuation. An enclosed car park must have a continuous supply of outdoor air to replace the air extracted together with the smoke.
Detailed requirements are laid down in national building and fire regulations and therefore differ from country to country. The principles described below are, however, common to most European regulations and design guidelines (e.g. CEN/TR 12101-5 [1] and EN 12101-13 [2]). In England, for example, the relevant guidance is given in Approved Document B, and smoke control in covered car parks is described in BS 7346-7.
Staircases in medium-rise and high-rise buildings – public buildings, hotels and other accommodation and, in many countries, also residential buildings – usually have to be enclosed, closed off with fire doors (e.g. of class EI 30) and fitted with smoke prevention (pressurisation) or smoke ventilation equipment.
Regulations also limit the travel distance to a protected staircase or final exit – separately for routes with one direction of escape and for routes with two or more alternative directions. If the staircase is not protected, the route along its flights and landings counts towards the travel distance, which may then exceed the permitted limit. Many regulations allow longer travel distances if the escape route is equipped with automatic smoke ventilation activated by a smoke detection system.
Enclosed car parks
Fire safety requirements for enclosed car parks typically cover:
- the maximum area of a fire compartment – which can usually be increased if the car park is protected by an automatic sprinkler system or if the parking spaces are separated by fire-resisting walls,
- automatic sprinkler protection of car parks with several underground levels,
- smoke extraction activated by a smoke detection system – usually required when the fire compartment has no direct vehicle entrance or exit to the outside or exceeds a specified area,
- the fire resistance of smoke extraction ducts (in sprinkler-protected car parks, regulations may require the integrity criterion E only),
- the number of escape exits from each fire compartment (usually at least two in larger car parks, one of which may be the vehicle entrance or exit), exits on every level and the maximum travel distance from a parking space to the nearest exit (shorter in enclosed than in open car parks),
- access to escape exits even when the vehicle entrance/exit or the gates between fire compartments are closed,
- separation of fire compartments from each other and from the above-ground part of the building by doors, gates or other closures with the required fire resistance (e.g. EI 30).
Evacuation conditions
Every place in a building intended for people must provide conditions for fast and safe evacuation from the endangered area, adapted to the number and physical condition of the occupants and to the function, construction and size of the building. This is achieved by technical fire safety measures, in particular:
- a sufficient number, height and width of escape exits;
- compliance with the permitted length, height and width of corridors and escape routes;
- fire-safe enclosure and separation of escape routes and rooms;
- protection of escape routes against smoke – by smoke prevention (pressurisation) or smoke extraction equipment and other technical solutions;
- emergency lighting (escape and standby lighting) in rooms and on escape routes;
- the possibility of broadcasting warning signals and voice messages via a voice alarm system in buildings where one is required.
The detailed evacuation conditions are specified by national building regulations.
How to design a fire protection system? What to bear in mind
Fire protection systems should be designed in parallel with the building and together with the other building services. A fire protection system should include suitable alarm devices that warn of a fire in the building, and it should be tailored to the type of building. There should be at least one fire alarm device in every part of the building.
A fire protection system comprises:
- detectors connected to alarm devices,
- the division of the building into fire compartments and detection zones,
- a defined method of supervising the installation and displaying its indications.
Many public buildings and multi-occupancy residential buildings are fitted with smoke control systems. They complement fire protection systems or form part of them. A smoke control system consists of:
- a control panel with an independent power supply,
- smoke detectors,
- smoke dampers or smoke vents,
- cabling with appropriate fire and temperature resistance,
- make-up air inlets.
Types of alarm devices in fire protection systems
The choice of fire alarm device depends on many factors, including the environment in which it will operate. By location, alarm devices are divided into indoor and outdoor devices. By the way they signal a fire, there are voice, visual, audible and combined devices. Alarm devices can also be conventional or addressable.
Fire protection installations should be designed so that they do not hinder evacuation.
Typical requirements for smoke extraction ducts with regard to integrity and smoke leakage (the exact classes and durations are set by national regulations and the fire strategy of the building):
- Ducts serving a single fire compartment should have at least class E600 S, with a fire resistance time at least equal to that of the building's floors. The lower class E300 S is permitted only if the design smoke temperature does not exceed 300 °C.
- Ducts serving more than one fire compartment should have at least class EI S, with a fire resistance time at least equal to that of the building's floors.
Typical requirements for smoke control dampers in smoke extraction ducts with regard to integrity and smoke leakage:
- Dampers serving a single fire compartment should be actuated automatically and have at least class E600 S AA, with a fire resistance time at least equal to that of the building's floors. The lower class E300 S AA is permitted only if the design smoke temperature does not exceed 300 °C.
- Dampers serving more than one fire compartment should have at least class EI S AA, with a fire resistance time at least equal to that of the building's floors.
Requirements for smoke extraction fans (EN 12101-3 [1]):
- class F600 60 – if the expected smoke temperature exceeds 400 °C,
- class F400 120 – in other cases, if the calculated smoke temperature and the safety of fire and rescue teams allow it.
Requirements for natural smoke and heat exhaust ventilators (smoke vents) in natural smoke ventilation (EN 12101-2 [1]):
- class B300 30 – for automatically opened ventilators,
- class B600 30 – for ventilators opened manually only.
All of the above smoke control components should be classified according to EN 13501-4 Fire classification of construction products and building elements – Part 4: Classification using data from fire resistance tests on components of smoke control systems [2]. Fire dampers can be controlled automatically (the damper is held in the standby position and closes when the temperature rises) or remotely (the damper operates in response to an external signal).
How to choose an installer for fire protection systems?
A fire protection installation follows the same rules as any other building service: first the design, then the installation. An experienced installer can spot design errors, the most common of which are:
- an incorrect sound level when selecting alarm devices,
- no synchronisation between alarm devices (audible and visual) operating in the same room,
- use of type A alarm devices (for indoor use) outdoors, chosen solely on the basis of their IP rating,
- alarm devices that do not cover the whole room,
- no visual alarm devices in rooms where audible alarms are insufficient.
Even a correctly designed fire protection installation will not work properly if the following points are neglected during installation:
- mounting alarm devices (both visual and audible) via a junction box or with short-circuit isolators,
- using fire-resistant cables between the control panel and the first alarm device and between junction boxes,
- fixing junction boxes to structural elements with adequate fire resistance,
- placing alarm devices in clearly visible locations,
- connecting devices to the correct type of power supply and using suitable cabling,
- adapting the cabling to components supplied at different voltages.
To avoid these errors, fire protection systems should be installed by people with experience in fire protection installations. Requirements for installers differ from country to country: in some, certification of the installing company is mandatory, in others there are voluntary third-party certification schemes – in the UK, for example, BAFE SP203-1 for fire detection and alarm systems. In any case, courses and training that end with an examination and an authorised installer certificate are an important indicator of competence. Such courses are run by distributors and manufacturers of fire protection systems. It is an advantage if the installer also holds electrical or telecommunications qualifications.
Use of fire dampers
Fire dampers in ventilation and air-conditioning systems are an important part of fire protection in buildings. This applies to all types of buildings (public buildings, residential buildings, production halls, warehouses, etc.) as well as to structures such as tunnels, metro systems, stations and underground passages.
Fire dampers – operating principle
Fire dampers limit the spread of smoke, fire and hot gases. In a fire, most deaths are caused by smoke poisoning; smoke also disorients people and makes evacuation more difficult. All fire dampers work on the same principle: in normal operation the fire damper is open, and in the event of fire it closes and shuts off the airflow [1].
Types of fire dampers
By type of actuation, there are:
- dampers with an electromagnetic release mechanism,
- dampers with a thermal release (fusible link or glass bulb),
- dampers with an electric actuator.
By shape, there are:
- rectangular dampers with a single blade,
- multi-blade dampers,
- circular dampers.
Smoke control dampers are a separate type of damper, different from fire dampers. A smoke control damper is part of the smoke extraction system and helps to remove smoke from the building. A fire damper, on the other hand, is part of the fire protection system, whose task is to prevent the spread of smoke and fire.
Smoke control dampers are installed in building elements (walls, floors, etc.). Their operating principle is the opposite of that of fire dampers: under normal conditions the damper is closed, and it opens when smoke appears (product standard EN 12101-8).
Building regulations in most European countries require the following:
Ventilation ducts and air-conditioning ducts passing through fire-separating elements (walls and floors between fire compartments) are fitted with fire dampers whose fire resistance class is equal to that of the separating element in terms of integrity, insulation and smoke leakage (E I S) [2].
Ventilation and air-conditioning ducts – exposed or enclosed – that pass through a fire compartment they do not serve have the fire resistance class required for the separating elements of that compartment (E I S) or are fitted with fire dampers at the compartment boundaries.
In fire compartments where a fire detection and alarm system is required, fire dampers are triggered by that system, irrespective of their thermal release.
Typical requirements for smoke control dampers in smoke extraction ducts (classification according to EN 13501-4):
- dampers serving only one fire compartment are actuated automatically and have class E600 S AA, with a fire resistance time at least equal to that of the building's floors; class E300 S AA is permitted if the calculated smoke temperature does not exceed 300 °C,
- dampers serving more than one fire compartment are actuated automatically and have class E I S AA, with a fire resistance time at least equal to that of the building's floors.
Fire dampers are selected according to the type of building. Ideally, the fire protection system of a building should be uniform (from a single manufacturer). The selection should take into account:
- integrity (E) – the ability of the damper to prevent the passage of flames and hot gases, and its resistance to deformation at high temperatures,
- insulation (I) – limiting the temperature rise of the damper surface on the side not exposed to fire,
- smoke leakage (S) – the ability of the damper to prevent the passage of smoke.
The fire resistance class of a fire damper should match that of the wall or floor in which it is installed. In special cases, dampers may be installed in elements with a lower fire resistance class, but the smoke leakage criterion must still be met.
Fire valves – what to look for when choosing them
Fire valves are installed at the terminals of general (comfort) ventilation systems and where ventilation ducts pass through building elements. They separate areas at risk of fire from the rest of the building. Depending on the direction of airflow, there are supply valves and extract valves.
Advantages of fire valves:
- fire resistance (usually up to EI 180 S),
- versions with an electromagnetic release available,
- installation in ceilings and walls,
- installation possible without connected ductwork.
For example, a fire valve installed in a building element with a ventilation duct connected on one side achieves integrity, insulation and smoke leakage performance of not less than 180 minutes. Fire valves are most often available in sizes DN 100, DN 125, DN 160 and DN 200.
It is worth stressing that fire valves are part of the fire safety system, so the relevant legal requirements must be observed. The main function of the valves is to regulate the airflow. Fire valves are installed so that their setting cannot change as a result of a rise in the temperature of the conveyed air.
Most manufacturers of fire valves use a release temperature of 72 °C. When the temperature of the air flowing through the valve exceeds 72 °C, the fusible link releases the spring and the valve closes tightly. The (intumescent) seals of the valves are usually made of polyurethane, and the fixings of galvanised steel or materials with similar properties.
A modern design combines a ventilation valve with a fire damper. The advantages of such designs are higher fire resistance, smaller dimensions and more configuration options. The main component is a fire damper in sizes 100, 125, 160 and 200 mm with low airflow resistance. The damper can be fitted with one or two limit switches that signal the current position of the blade.
How to choose ducts and fittings for a smoke extraction system?
The purpose of smoke extraction systems is to remove hot gases and smoke from the fire area and to create smoke-free zones, enabling firefighting and the evacuation of people. The basic component of a smoke extraction system is smoke extraction ducts, which have two functions: they convey air like ordinary ventilation ducts and they extract smoke from the fire compartment.
Building regulations typically require a smoke extraction system to:
- remove smoke at a rate which ensures that, for the time needed to evacuate people, protected corridors and escape routes remain free of smoke or temperatures that would prevent safe evacuation,
- have a continuous supply of outdoor air to replace the air extracted together with the smoke.
Smoke extraction ducts (EN 12101-7 [1], tested according to EN 1366-9 or EN 1366-8 [2]) serving:
- only one fire compartment typically have class E600 S, with a fire resistance time at least equal to that of the building's floors; class E300 S is permitted if the calculated smoke temperature does not exceed 300 °C,
- more than one fire compartment have class EI S, with a fire resistance time at least equal to that of the building's floors.
What should a smoke extraction system be made of?
A smoke extraction system must be made of appropriately classified materials and components. Smoke extraction ducts are most often made of sheet steel with a rectangular or circular cross-section. At high temperatures, sheet steel expands (at approx. 600 °C by about 7–9 mm per metre), which can cause the ducts to lose their tightness and allow fire and smoke to spread. That is why smoke extraction systems include expansion joints and flexible connectors. The role of expansion joints can also be taken over by suitably shaped ducts.
Their main task is to compensate for the elongation of the duct caused by high temperatures during a fire. The duct joints, made of materials resistant to high temperatures, are also important. Less common are ducts made of fire-resistant gypsum boards, mineral wool boards or mats, glass fibre, vermiculite boards, silicate-cement boards and silicate boards.
Ventilation systems also include silencers, which may form part of a comfort ventilation system that also serves as the smoke extraction system. In this case the sound-absorbing material is very important, as it must withstand high temperatures. Silencers for smoke extraction systems are now available that also act as expansion joints.
How should fire protection systems be maintained?
To maximise the fire safety of buildings, fire protection systems must be inspected and maintained regularly. In most countries the building owner or operator is legally responsible for the maintenance of fire protection systems. Maintenance should be carried out as often as the manufacturers specify, but usually at least once a year – national regulations may set the intervals in more detail. Hose reels and hydrant hose systems are inspected every year, and their hoses are pressure-tested every five years [2].
Apart from legal requirements, there are other reasons for inspecting a system. The most common are failures, hidden defects, incorrect installation, external and weather-related factors, and mechanical damage.
Inspections and maintenance of fire protection systems may only be carried out by properly trained persons. Specialists should have the skills and authorisations required to inspect, service and, if necessary, repair the system in question. A person without the appropriate skills and authorisations must not maintain or repair fire protection systems.
CEN/TS 54-14:2004 [1] provides guidelines for the planning, design, installation, commissioning, use and maintenance of fire detection and fire alarm systems. According to clause 4.8, natural or legal persons carrying out any of the work covered by the guidelines should have appropriate competence, experience and qualifications. Clauses 7.7 (installation) and 8.6 (commissioning) state that this work should be carried out by persons with appropriate theoretical and practical knowledge and qualifications. Only clause 11.8 (maintenance) states explicitly that maintenance requires trained specialists.
Technical inspections of smoke control systems are carried out in accordance with national regulations, the relevant standards and the manufacturer's operation and maintenance documentation. Most manufacturers require inspections twice a year (every 6 months). If the manufacturer recommends inspections more often than once a year, they must be carried out at the frequency specified by the manufacturer.