SSCL-SMO/SSL-SMO full segmented collar saddle, fire resistance class:
E600 120 (ho) S1500 single, designed for single-compartment smoke
extraction systems and combined (dual-function) systems.
It is available in a symmetrical and asymmetrical version, it is equipped
with GASK two double seals for ventilation fittings made of EPDM and
a 1.8 mm thick and 10 mm wide intumescent seal. Welding points and other
joints are covered with high-temperature sealant, which use is required
during assembly in a duct.
SMOKE System fittings are available in diameters from 100 to 1000 mm.