Single Smoke Extraction Damper for Fire Ventilation Systems
SEDS
Single Smoke Extraction Damper
Single smoke extraction dampers are critical components of fire ventilation systems, designed to effectively remove smoke, heat, and combustion products from individual fire compartments. They act as automatic shutters in ventilation ducts, opening in the event of a fire to ensure safe evacuation and facilitate the work of emergency services. Equipped with an actuating mechanism, they can also be operated manually.
Key Features
Fire resistance classification E600 90 (ve-i-o) S1000C300AAsingle according to EN 13501-4.
Designed for smoke and heat removal from single fire compartments.
Casing made of galvanized plate without additional surface finish.
Damper blades made of fire-resistant asbestos-free mineral fiber boards.
Maximum air flow velocity up to 15 m/s.
Resistance to underpressure up to -1000 Pa and overpressure up to 500 Pa.
Suitable for installation with a horizontal blade axis.
Equipped with Belimo or Schischek InMax actuating mechanisms, with manual override capability.
Integrated terminal switches for "OPEN" and "CLOSED" position signaling.
Wide range of available dimensions, with reinforcement profiles for larger sizes.
Compliance with EN 1366-9 and EN 12101-8 standards.
Technical Data
Parameter
Value
Classification
E600 90 (ve-i-o) S1000C300AAsingle
Max. air velocity
15 m/s
Max. underpressure
-1000 Pa
Max. overpressure
500 Pa
Operating temperature
-20°C to +50°C
Non-operating temperature
-40°C to +80°C
Casing material
Galvanized steel plate
Blade material
Fire-resistant asbestos-free mineral fiber boards
Actuating mechanism
Belimo BLE24/BE24-12/BE230/BE230-12 or Schischek InMax 50.75-S