Multi Smoke Dampers (MSD) are essential components in smoke exhaust duct systems, specifically engineered to effectively remove smoke, heat, and combustion products from fire-affected compartments. In the event of a fire, the fire ventilation system automatically opens the damper in the affected section, facilitating the rapid extraction of harmful substances. These dampers are fire-resistant and designed for systems with automatic activation, suitable for installation within the fire compartment construction.
| Parameter | Value |
|---|---|
| Nominal Voltage | AC 24V/230V or DC 24V (depending on actuator) |
| Degree of Protection | IP 54 (for Belimo actuators), IP 66 (for Schischek InMax) |
| Ambient Temperature Range (operating) | -20°C to +50°C |
| Ambient Temperature Range (non-operating) | -40°C to +80°C |
| Maximum Air Velocity | 15 m/s |
| Maximum Underpressure | -1500 Pa |
| Maximum Overpressure | 500 Pa |
| Internal Leakage Classification | min. class 2 (round), min. class 2 (square) |