In stock

Multi Smoke Round Damper for Smoke Extraction Systems

MSD
Photo of product MSD

Multi Smoke Damper for Smoke Extraction Systems

Multi smoke dampers (MSD) are shutters used in smoke exhaust duct systems. Their primary function is to effectively remove smoke, heat, and combustion products from affected fire compartments. In the event of a fire, the smoke and fire ventilation system opens the damper in the affected section to quickly remove harmful substances. The dampers are fire resistant, designed for systems with automatic activation, and can be installed in fire compartment constructions.

Key Features

  • CE certified according to EN 12101-8.
  • Tested in accordance with EN 1366-10.
  • Fire classification EI 120 (according to EN 13501-4+A1).
  • Minimum external casing leakage class: C (according to EN 1751).
  • Minimum internal leakage class: 2 for round dampers (from 560 mm to 630 mm) and square dampers (up to 1500x800 mm), 3 for others.
  • Cycling test in class C 10000 (according to EN 15650).
  • Maximum air velocity: 15 m/s.
  • Operating pressure range: underpressure up to -1500 Pa, overpressure up to 500 Pa.
  • Permissible ambient temperature: from -20°C to +50°C.
  • Damper body made of galvanized plate, blades made of fire-resistant asbestos-free mineral fiber boards.

Technical Data

Parameter Value
Nominal Voltage AC 24V/230V, DC 24V
Power Consumption (motoring) 5 W to 12 W
Power Consumption (holding) < 1 W to 2.5 W
Degree of Protection IP 54 / IP 66
Running Time for 95° < 30 s to < 60 s
Ambient Temperature Range -30°C to +50°C
Non-Operating Temperature -40°C to +80°C
Connection (motor) Cable 1m, 3 x 0.75 mm²
Connection (auxiliary switch) Cable 1m, 6 x 0.75 mm²

 

 

 