FDA2-12-M / FDA2-12-T
Photo of product FDA2-12-M / FDA2-12-T

The FDA2-12 round fire dampers are designed for use in
general ventilation systems to seal off smoke and fire between
adjacent fire partitions.
The fire dampers are classified according to EN 13501-3+A1:2010P
(Fire classification of construction products and building
elements). The fire resistance was tested as per PN-EN 1366-
2:2015 (Fire resistance tests for service installations — Part 2:
Fire dampers). The entire manufacturing process meets the
requirements of EN 15650:2010.
The FDA2-12 fire dampers can be installed in horizontal and
vertical fire partitions to provide fire resistance of EI 120
(ve ho i↔o) S (which may depend on the actual fire resistance
of the partition).

Sprawdź parametry techniczne produktu

Fire Dampers - Products range
Miniature picture Product code Name of product Files to download
Photo of product Round fire dampers FDA2-12-M with access door FDA2-12-T

Round fire dampers FDA2-12-M with access door

The FDA2-12 round fire dampers are designed for use in
general ventilation systems to seal off smoke and fire between
adjacent fire partitions.
The fire dampers are classified according to EN 13501-3+A1:2010P
(Fire classification of construction products and building
elements). The fire resistance was tested as per PN-EN 1366-
2:2015 (Fire resistance tests for service installations — Part 2:
Fire dampers). The entire manufacturing process meets the
requirements of EN 15650:2010.
The FDA2-12 fire dampers can be installed in horizontal and
vertical fire partitions to provide fire resistance of EI 120
(ve ho i↔o) S (which may depend on the actual fire resistance
of the partition).

Round fire dampers FDA2-12-M with access door
Photo of product Rectangular fire dampers FDA2-12 with access door FDA2-12-M / FDA2-12-T

Rectangular fire dampers FDA2-12 with access door

The FDA2-12 round fire dampers are designed for use in
general ventilation systems to seal off smoke and fire between
adjacent fire partitions.
The fire dampers are classified according to EN 13501-3+A1:2010P
(Fire classification of construction products and building
elements). The fire resistance was tested as per PN-EN 1366-
2:2015 (Fire resistance tests for service installations — Part 2:
Fire dampers). The entire manufacturing process meets the
requirements of EN 15650:2010.
The FDA2-12 fire dampers can be installed in horizontal and
vertical fire partitions to provide fire resistance of EI 120
(ve ho i↔o) S (which may depend on the actual fire resistance
of the partition).

Rectangular fire dampers FDA2-12 with access door
Photo of product Round fire dampers FDA2-12-M with access door and actuator FDA2-12-M

Round fire dampers FDA2-12-M with access door and actuator

The FDA2-12 round fire dampers are designed for use in
general ventilation systems to seal off smoke and fire between
adjacent fire partitions.
The fire dampers are classified according to EN 13501-3+A1:2010P
(Fire classification of construction products and building
elements). The fire resistance was tested as per PN-EN 1366-
2:2015 (Fire resistance tests for service installations — Part 2:
Fire dampers). The entire manufacturing process meets the
requirements of EN 15650:2010.
The FDA2-12 fire dampers can be installed in horizontal and
vertical fire partitions to provide fire resistance of EI 120
(ve ho i↔o) S (which may depend on the actual fire resistance
of the partition).

Round fire dampers FDA2-12-M with access door and actuator
Photo of product Circular shut-off fire dampers with an actuator FDA-12-M

Circular shut-off fire dampers with an actuator

The FDA-12 round shut-off fire dampers used in the general ventilation systems as protections that prevent smoke and fire from getting between the separated neighbouring fire zones.
The shut-off dampers in question have been classified in accordance with the procedures included in PN-EN 13501-3+A1:2010P (fire classification of construction products and building elements). The fire tests have been carried out in
accordance with PN-EN 1366-2:2001P (Fire resistance tests for service installations - Part 2: Fire dampers). All the production activities are in conformance with PN-EN 15650:2010.
The FDA-12 shut-off dampers may be used in vertical and building partitions, ensuring the fire rating of EI 120 ( ve ho i <-> o ) S (depending on the fire rating class of the building partition)

Circular shut-off fire dampers with an actuator
Photo of product Circular shut-off fire damper with spring and a thermal fuse FDA-12-T

Circular shut-off fire damper with spring and a thermal fuse

The FDA-12 round shut-off fire dampers used in the general ventilation systems as protections that prevent smoke and fire from getting between the separated neighbouring fire zones.
The shut-off dampers in question have been classified in accordance with the procedures included in PN-EN 13501-3+A1:2010P (fire classification of construction products and building elements). The fire tests have been carried out in
accordance with PN-EN 1366-2:2001P (Fire resistance tests for service installations - Part 2: Fire dampers). All the production activities are in conformance with PN-EN 15650:2010.
The FDA-12 shut-off dampers may be used in vertical and building partitions, ensuring the fire rating of EI 120 ( ve ho i <-> o ) S (depending on the fire rating class of the building partition)

Circular shut-off fire damper with spring and a thermal fuse
Photo of product Fire damper 100x100 mm to 1000x500 mm FDMB

Fire damper 100x100 mm to 1000x500 mm

Fire dampers are shutters in ducts of air-conditioning devices that prevent spreading
the fire and combustion products from one fire segment to the other one by means
of closing the duct in the points of fire separating constructions.

Dampers blade automatically closes air duct using a shutting spring or
an actuating mechanism back spring. Closing spring is released either by pushing
of the button or by thermal fuse.The back spring of the actuating mechanism is started
when the thermoelectrical starting mechanism BAT is activated, when a reset button on
BAT is pushed or when a power supply of the actuating mechanism is stopped.

The fire damper is sealed with a silicon packing against smoke penetration after
closing the blade. At the same time, the damper blade is bedded in a material which
enlarges its capacity and air proofs the air duct.

Characteristics

  • Dampers from 100 × 100 mm to 1 000 × 500 mm
  • CE certified acc. to EN 15650Tested in accordance with EN 1366-2
  • Classified acc. to EN 13501-3+A1
  • Fire resistance up to EIS 120 - 500 Pa
  • External Casing leakage class C
  • Internal leakage class 2 acc. to EN 1751
  • Corrosion resistant acc. to EN 15650
  • Cycling test in class C 10 000 acc. to EN 15650
  • Damper actuating mechanical, or electrical
  • Maximum airspeed through opened damper of 12 m/s and pressure difference 1200 Pa
Fire damper 100x100 mm to 1000x500 mm
Photo of product Fire damper EIS 60 FDMR-60

Fire damper EIS 60

Fire dampers are shutters in ducts of air-conditioning devices that prevent spreading
the fire and combustion products from one fire segment to the other one by means
of closing the duct in the points of fire separating constructions.

The damper blade automatically closes the air duct using a shutting spring or
an actuating mechanism of back spring. The shutting spring is activated by pressing
the start button or by the impulse from the thermal fuse. The back spring of
the actuating mechanism is started when the thermoelectric starting mechanism BAT
is activated, when the reset button on BAT is pressed or when the power supply to
the actuating mechanism is stopped.

After closing the blade, the damper is sealed with a silicon packing against smoke
penetration. The damper can be delivered with a seal without silicone at
the customer's wish. At the same time, the damper blade is embedded in a material which enlarges its volume due to increasing temperature and hermetically seals the air duct. The dampers have one inspection hole, as the shutting device and the inspection hole can be set to the most advantageous position with respect to operation and handling of the control device by turning the damper a little in case of the spiro model of the dampers.

Fire damper characteristics

  • CE certified acc. to EN 15650
  • Tested in accordance with EN 1366-2
  • Classified acc. to EN 13501-3+A1
  • Fire resistance EIS 60
  • External Casing leakage class C, Internal leakage class 3 acc. to EN 1751
  • Cycling test in class C 10000 acc. to EN 15650
  • Corrosion resistant acc. to EN 15650
  • ES Certificate of conformity No. 1391-CPR-2019/0161/O1
  • Declaration of Performance No. PM/FDMR60/01/20/1
  • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b
Fire damper EIS 60
Photo of product Fire damper FDMD FDMD Fire damper FDMD
Photo of product Circular fire damper ø100 to ø800 mm FDMR

Circular fire damper ø100 to ø800 mm

Fire dampers are shutters in ducts of air-conditioning devices that prevent spreading
the fire and combustion products from one fire segment to the other one by means
of closing the duct in the points of fire separating constructions.

The damper blade automatically closes the air duct using a shutting spring or
an actuating mechanism of back spring. The shutting spring is activated by pressing
the start button or by the impulse from the thermal fuse. The back spring of
the actuating mechanism is started when the thermoelectric starting mechanism BAT
is activated, when the reset button on BAT is pressed or when the power supply to
the actuating mechanism is stopped.

After closing the blade, the damper is sealed with a silicon packing against
smoke penetration. The damper can be delivered with a seal without silicone at
the customer's wish. At the same time, the damper blade is embedded in a material
which enlarges its volume due to increasing temperature and hermetically seals
the air duct.
The dampers have one inspection hole, as the shutting device and the inspection
hole can be set to the most advantageous position with respect to operation
and handling of the control device by turning the damper a little in case of
the spiro model of the dampers.

Damper characteristics

  • CE certified acc. to EN 15650
  • Tested in accordance with EN 1366-2
  • Classified acc. to EN 13501-3+A1
  • Fire resistance: EIS 120 - 500 Pa, EIS 90, EIS 60
  • External Casing leakage class C, Internal leakage class 3 acc. to EN 1751
  • Cycling test in class C 10000 acc. to EN 15650
  • Corrosion resistant acc. to EN 15650
  • ES Certificate of conformity No. 1391-CPR-2020/0004
  • Declaration of Performance No. PM/FDMR/01/21/1
  • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b

 

Circular fire damper ø100 to ø800 mm