In stock

Fire-resistant ventilation reducer for smoke extraction systems E600 120 (h)

RSCLL-SMO/RSCLFL-SMO/RSLL-SMO/RSLFL-SMO
Photo of product RSCLL-SMO/RSCLFL-SMO/RSLL-SMO/RSLFL-SMO

Fire-resistant Ventilation Reducer SMOKE System

SMOKE System segmented spigot reducers are essential components for ventilation systems, designed to ensure fire safety. They feature E600 120 (h) S1500 single fire resistance, making them ideal for both single-zone and dual-function smoke extraction systems. These fittings are equipped with double-lip GASK EPDM gaskets and an additional intumescent gasket (1.8mm thick, 10mm wide), guaranteeing tightness and reliability. Weld points and other connections are covered with high-temperature sealing compound, and the product is available in a wide range of diameters from 100 to 1000mm.

Key Features

  • E600 120 (h) S1500 single fire resistance
  • Designed for single-zone and dual-function smoke extraction systems
  • Equipped with double-lip GASK EPDM gaskets
  • Additional intumescent gasket (1.8mm thick, 10mm wide)
  • Connection points covered with high-temperature sealing compound
  • Available in diameters from 100 to 1000mm
  • Made from galvanized steel
  • Available types: symmetric spigot-spigot (RSCLL-SMO), symmetric socket-spigot (RSCLFL-SMO), asymmetric spigot-spigot (RSLL-SMO), asymmetric socket-spigot (RSLFL-SMO)

Technical Data

Ød1 [mm] Ød2 [mm] Sheet thickness t [mm] L [mm] Weight [kg]
125 100 0,7 52 0,39
200 100 0,7 135 0,75
300 150 0,7 208 1,51
500 250 0,7 276 3,16
800 400 0,9 447 9,57
1000 500 0,9 592 15,15

 

 